When you click on links to various merchants on this site and make a purchase, this can result in this site earning a commission. Affiliate programs and affiliations include, but are not limited to, the eBay Partner Network.
Store Categories Store Categories GEYA Dual Power Automatic Transfer Switch( Grid - Generator)
Product Description
General
Application
Residence,and in various occasions where continuous power failure is not allowed.
Function
Auto mode:Common power supply must be City Grid Power. Backup power must be AC genarator.When there is only one power supply is working, the product will automatically switch to that power supply. When the common power supply and the backup power supply are supplied at the same time, the common power supply is used Preferentially.
(Attention: in automatic mode, forcibly rotating the power switch handle will cause damage to the transfer switch)
Manual mode: Power supply should be transfered manually by rotating the handle.
How to choose item
One Live line Voltage Suitable for US voltage system Must connect with Neural line Product you should choose 110V 110/220V 1 Live line + 1 Neutral live 2P-100A-110VCLICK HERE
2 Live line + 1 Neutral live 3P-100A-110VCLICK HERE 3 Live line + 1 Neutral live 4P-100A-110VCLICK HERE 220V 220V/400V 1 Live line + 1 Neutral live 2P-63A-220VCLICK HERE 1 Live line + 1 Neutral live 2P-100A-220VCLICK HERE 2 Live line + 1 Neutral live 3P-100A-220VCLICK HERE 3 Live line + 1 Neutral live 4P-100A-220VCLICK HERE NOTE:85% Us~110% Us
Technical Parameters
Item No.
W2R
Rated current 100A
Rated insulation voltage
AC690V
Rated controlvoltage
AC220V (-15%~+10%);50~60Hz
Signal terminalrated voltage AC220V Grade PC Level: able to male and withstand, not to break short-circuit current
Use category
AC-33iB
Rated impulse withstand voltage
8KV
Life
Electrical:2000times; Mechanical: 5000times
Rated limited short-circuit current Iq
50KA
SCPD (FUSES )
RT16-00-63A
Contact transfer time
<50ms
Operating transfer time
<50ms
Return transfer time
<50ms
Off-time
<50ms
Packing List
1 PCS automatic transfer switchand 1PCS Rail and manual book
Q&A
1. Common power supply must be City Grid Power. Backup power must be AC genarator OR City Grid Power!
2. In auto mode, signal terminal AR&AN and BR&BN must be wired to common power supply and backup supply. Or product can not work!
3. Suggestingadd over&under voltage protector to circuit protect productfrom being burnt due to under-voltage or over-voltage.